GeoStudysGEOTECHNICS | ENVIRONMENT | GEOTHERMAL
Technical articles  /  03 · Geothermal
GeoStudysTechnical articles
ISSUE 1 · SEPTEMBER 2026 · GEOTHERMAL
Technical article 03Shallow geothermal · Borehole heat exchangers

BHE field and balance ratio over 25 years

Why BHE fields cool down – and what thermal recharge decides

Download PDF A4 · 1 PAGEREADING TIME APPROX. 3 MINUTES · AS OF 25 SEPT 2026
Abstract

A BHE field is not a well but a store. If, year after year, far more heat is extracted from a dense field than is returned, the fluid temperature falls over decades. The article explains the balance ratio and the line-source calculation and shows, with a study for a hotel resort on the Baltic coast, that recharge decides between operation and depletion.

KEYWORDS · Borehole heat exchangers · BHE field · Balance ratio · Regeneration · VDI 4640 · Long-term simulation

1Background

Systems up to 30 kW are designed from tabulated values, which VDI 4640 Part 2 relates to 50 years of operation [1], [4]. In a dense field, the cooled zones of neighbouring boreholes overlap; the centre cools more, increasingly each year. Larger systems must therefore be simulated with the actual load profile.

2Balance ratio

The ratio of heat returned to heat extracted governs:

β = Qrec / Qext(1)

Qext annual heat extraction · Qrec annual thermal recharge from cooling, solar thermal, waste heat or surface water

With β close to 1, the field acts as a seasonal store. With small β, the temperature of dense fields drifts over decades. Back-analyses of monitored Swiss fields confirm the model; if anything, it overestimates the cooling [3].

3Calculation

Each borehole acts as a line source; superposed in time and space, the following applies [5]. The infinite line source overestimates the cooling (safe side); g-functions capture end effects [2].

ΔT(r,t) = q′ / (4πλ) · E1(r² / (4at))Tf = T0 − ΣΔT − q′·Rb(2)

q′ extraction per metre · λ thermal conductivity · a = λ/(ρc) · Rb borehole thermal resistance · Tf mean fluid temperature

Minimum mean fluid temperature over 25 years for six variants — anonymised
← SWIPE IMAGE SIDEWAYS →
Figure 1. Minimum mean fluid temperature over 25 years, six variants (boreholes × length) on a 7 m grid (hotel resort study, Baltic coast, anonymised; infinite line source, λ = 2.3 W/(m·K), T0 = 10 °C, Rb = 0.09 m·K/W). Only with 95 % recharge does the field stay above the criterion; the other variants fail it long before the 50 years to which SIA 384/6 refers.

4Example: hotel resort

A hotel with year-round base load is to extract approx. 1 410 MWh/a from the field; cooling returns only approx. 18 %. Criterion: mean fluid temperature ≥ −1.5 °C to SIA 384/6 [6]; VDI 4640 Part 2 leaves the limit open. Lower load (S4), a smaller field with lower load (S5) and shorter boreholes (S6) fail it at β of 27 to 50 %. Only 95 % recharge from seawater keeps the fluid at approx. +1 °C after 25 years.

Table 1. Minimum mean fluid temperature in year 25 (calculated)
CaseBoreholes × lengthExtractionβTf,min
S180 × 150 m118 kWh/(m·a)18 %−41 °C
S280 × 150 m118 kWh/(m·a)50 %−23 °C
S380 × 150 m118 kWh/(m·a)95 %approx. +1 °C
S480 × 150 m70 kWh/(m·a)30 %−16 °C
S548 × 150 m69 kWh/(m·a)50 %−6 °C
S680 × 100 m118 kWh/(m·a)27 %−36 °C

5Recommendations

  • Derive the balance ratio from the load profile before fixing borehole number and length; plan recharge explicitly.
  • Simulate over the service life, usually 50 years; agree the limit temperature with the water authority early.
  • Confirm λ and Rb by a thermal response test [7] before sizing.
Standards and references
  1. VDI 4640 Part 2:2019-06 Thermische Nutzung des Untergrunds – Erdgekoppelte Wärmepumpen
  2. Eskilson, P. (1987) Thermal Analysis of Heat Extraction Boreholes. PhD thesis, Lund
  3. Pahud, D. (2015) Simulationen gemessener Erdwärmesondenfelder. Final report, BFE, Bern
  4. Schäfer, I. (2019) Auswirkung der neuen VDI 4640 Blatt 2 auf die Planung. 5. Willicher Praxistage, 6 Nov. 2019
  5. Carslaw, H. S.; Jaeger, J. C. (1959) Conduction of Heat in Solids. 2nd ed., Oxford
  6. SIA 384/6:2021 Erdwärmesonden
  7. VDI 4640 Part 5:2020-07 Thermal Response Test
GEOSTUDYS TECHNICAL ARTICLES · ISSUE 1 · 2026 · ARTICLE 03WWW.GEOSTUDYS.COM

SUGGESTED CITATION: GeoStudys Consulting (2026): BHE field and balance ratio over 25 years. GeoStudys Technical articles, Issue 1, Article 03. www.geostudys.com/en/technical-articles/bhe-field-balance-ratio.html